AX-GS-CM-NO2-M / CO 0-300ppm , NO2 0-10ppm transmitter, RS485 Modbus POA Qty
Add –R to the part number for rear cable entry , Add –B for Black Enclosure / POA Qty
 <<  |  <  | OVERVIEW | SPECIFICATION | DATASHEETS        

The AX-GS-CM-NO2-M is an ideal solution for detecting harmful emissions in parking garages, loading docks, warehouses etc. It offers detection of carbon monoxide and nitrogen dioxide gases in the same enclosure . Sensor readings are transmitted over RS-485 Modbus RTU protocol. By monitoring the levels of CO and NO2 in the air, the ventilation system can be adjusted to ensure that the air quality is within safe limits.
Product Features
• Detection range - CO: 0 to 300 ppm ,NO2: 0 to 10ppm
• Isolated RS485 output
• Electrochemical sensing elements
• Zero and sensitivity adjustments for field calibration
• Easy installation with plug-in connections
• UL listed sensors: File no. E240671

Power Supply
24Vac ±10%, 100mA maximum or 24Vdc ± 10%, 60mA maximum
Sensor Type (CO and NO2)
Electrochemical 3-electrode
Output Range
CO
Output Accuracy
CO
Response time(t90)
< 35 seconds
Long term sensitivity drift
CO
Typical Coverage Area
700m² or 15m radius
Settling Time
3 minutes after power up
Life Expectancy
NO2
Ambient Temperature & Humidity
0-50°C, 15-90% RH non-condensing
Housing
Flame retardant ABS, IP65 White ( optional Black-see order codes)
Dimensions & Weight
92mm diameter x 52mm, 180gms
Terminals
Rising clamp for 0.5-1.5mm² , 2 Part Pluggable
Communication

Protocol
M odbus RTU protocol over RS485
Address range
1-63 (settable using dipswitch), 1-247 (settable using configuration register)
Baud rates supported
9600bps,19200bps,38400bps,57600bps,115200bps
Parity
None (default), Odd, Even (odd, even selectable via configuration register)
Number of stop bits
1(default),2 (2 is selectable via configuration register)
Isolation
1500VDC (60sec, <1mA leakage current) between Power and Output
120Ohms termination
Available on board. Enabled using jumper
Recommended cable
24AWG twisted pair shielded cable (1 pair for data and 1 conductor for common)
Maximum devices on a network
32
Warranty
5 years for the product. (NO2 sensor